Test
Protocol
To test the Alter-Air
cooler at various temperatures and humidity levels, the company created
an ambient air simulator. The
heat pump (1) warms air
to designated levels (can reach 115 degrees) and blows the heated air
through a humidifier (2)
which adds humidity (at levels we designate and control) to the air.
The moist and heated
air is mixed in the mixing
chamber (3) and becomes simulated ambient air. This air is then
routed directly into the test
chamber (5) which insures that the test chamber is warm and humid.
Inside temperatures and humidity levels are read from gauges located
outside the test chamber.
When the test chamber
reaches ambient air conditions, the air from the mixing chamber is then
presented to the Alter-Air
cooling system (ACE) (4)
which is then turned on. The air for that test (designated temperature
and humidity level) is drawn into the cooling system.
The air cooled by the
system is then blown into the
test chamber (5)
Air in the test
chamber is returned to the Alter-Air cooling system by the
return air duct (6)
Exhaust air, 15 t0 25
degrees below ambient air, is exhausted through the
exhaust air duct (7)
Measurement Points (Reading the Test)
The temperature and
relative humidity (RH) of the air entering the mixing chamber is
established at the start of each test. Gauges are set at the entry port
of the Alter-Air cooling system to ensure that these remain constant
through out the test.
The temperature and
RH of the air leaving the cooling system and entering the test chamber
are noted to determine the effectiveness of the cooling system.
The temperature and
the RH of the test chamber are read at ten minute intervals to determine
the rate at which the test chamber is cooled. The temperature of the
return air is also read at ten minute intervals, as is the temperature
and RH of the exhaust air.
At the end of an hour
the test is deemed complete and final readings are taken. The test also
measures the water and power consumption during the test.